PRODUCTION PHOTO
TECHNICAL SPECIFICATION
Micro module |
Sizes |
Single row cold/hot air channels (L*W*H) |
Double-row cold/hot air channels L*W*H) |
||
Number of cabinets supported |
Single row ≤ 24 cabinets, double row ≤ 48 cabinets |
|
Alignment |
Incoming and outgoing lines |
|
Door opening mode |
Automatic sliding door/sliding doors |
|
Roof type |
Self-resetting flip-up roof/ drop-down flip-up roof / fixed roof |
|
Installation |
Can be installed directly on the cement floor or on a raised floor |
|
Cabinet |
Sizes(H*W*D) |
2000*600/800*1200mm;2000*600/800*1100mm 2200*600/800*1200mm |
Usable space |
42U/47U |
|
Ventilation rate |
Front and rear door mesh door design, through-hole rate ≥ 75% |
|
IP rating |
IP20 |
|
Cabinet Load |
≤1.5t |
|
Precision air-conditioning between columns |
Cooling capacity |
25kW/35kW/46kW165kW |
Indoor unit sizes(H*W*D) |
2000*300*1100mm(25kW), 2000*300*1200mm(35kW), |
|
Input Power |
380/400/415VAC,50160Hz,3Ph+N+PE |
|
IP rating |
Internal IP23, External IP55 |
|
Precision power distribution cabinets at the head of the column |
Input Voltage |
380/400/415VAC,50160Hz,3Ph+N+PE |
Input Switch Specifications |
160a/250a/400a/630a |
|
Output Specification |
IT:40A/1P,63A/1P,40A/3P,63A/3P,Max support 144 output air switches |
|
AC lightning protection |
20kA, 8/20μs |